PSYCHROMETRICS • LESSON 9

Moisture Removal and Air-Conditioning Calculations

Psychrometric calculations turn entering-air, leaving-air, and airflow measurements into estimates of moisture removal and air-side cooling capacity.

This lesson uses one cooling-and-dehumidification example to practice the calculation process. The goal is to keep the properties, units, and field meaning clear—not to replace load calculations, equipment ratings, or manufacturer service procedures.

What You Will Learn

1

Read humidity ratio, enthalpy, and specific volume at plotted air conditions.

2

Calculate moisture and enthalpy differences across a cooling coil.

3

Convert cfm to dry-air mass flow using specific volume.

4

Estimate total air-side cooling capacity from mass flow and enthalpy difference.

5

Estimate condensate removal from mass flow and humidity-ratio difference.

6

Interpret sensible, latent, and total capacity without treating an estimate as a building load.

A Calculation Cannot Correct a Poor Measurement

Measure the same airstream before and after the process under stable operation. Confirm instrument accuracy, measurement locations, airflow, operating mode, outdoor-air position, and the barometric-pressure basis of the chart or software.

The example uses 5,000 cfm of air entering at 95°F dry bulb and 75°F wet bulb and leaving at 70°F dry bulb and 55°F wet bulb. Approximate chart readings are shown below and may vary slightly with chart resolution and rounding.

ENTERING AIR

95°F DB and 75°F WB

Humidity ratio ≈ 98 grains/lb dry air, enthalpy ≈ 38.3 Btu/lb dry air.

LEAVING AIR

70°F DB and 55°F WB

Humidity ratio ≈ 40 grains/lb dry air, enthalpy ≈ 23.1 Btu/lb dry air, specific volume ≈ 13.5 ft³/lb dry air.

Keep Every Property on a Dry-Air Basis

Psychrometric-chart humidity ratio, enthalpy, and specific volume are commonly expressed per pound of dry air. Keep that basis visible throughout the calculation so unlike quantities are not mixed.

Enthalpy Combines Sensible and Latent Energy

Enthalpy is a convenient measure of the combined sensible and latent energy of moist air. After locating the state point, follow the chart’s enthalpy direction to the enthalpy scale and read the value in Btu per pound of dry air.

Psychrometric chart showing how to read an enthalpy of approximately 26.3 Btu per pound of dry air at 80 degrees Fahrenheit dry bulb and 60 degrees Fahrenheit wet bulb
Figure 1. Follow the enthalpy line diagonally up and left from the plotted state point to read enthalpy on this chart.
Capacity Uses an Enthalpy Difference

One enthalpy value describes one state. Cooling effect per pound of dry air is the entering enthalpy minus the leaving enthalpy.

Subtract Humidity Ratios, Not Relative Humidity

For a cooling-and-dehumidification process, subtract the leaving-air humidity ratio from the entering-air humidity ratio. In the example, 98 − 40 gives approximately 58 grains of water removed per pound of dry air.

Psychrometric chart comparing entering air at about 98 grains per pound of dry air with leaving air at about 40 grains per pound and showing about 58 grains per pound removed
Figure 2. The humidity-ratio difference is water removed per pound of dry air, not the total condensate rate.

Correct Property

Use humidity ratio in grains of water per pound of dry air.

Correct Direction

For cooling and dehumidification, use entering humidity ratio minus leaving humidity ratio.

Correct Meaning

The result applies to each pound of dry air and must still be multiplied by dry-air mass flow.

Find the Total Cooling Effect per Pound of Dry Air

Subtract leaving-air enthalpy from entering-air enthalpy. The example gives 38.3 − 23.1 = 15.2 Btu/lb dry air. That difference includes both sensible and latent cooling.

Psychrometric chart showing entering enthalpy of about 38.3 and leaving enthalpy of about 23.1 Btu per pound of dry air for an enthalpy difference of 15.2
Figure 3. The 15.2 Btu/lb dry air difference is the total cooling effect for each pound of dry air passing through the process.

Rounding: Carry extra digits when possible and round the final answer. Values read from a printed chart are approximate, so small differences are expected.

Use Specific Volume to Convert CFM

CFM is cubic feet per minute, but psychrometric properties are based on pounds of dry air. Specific volume connects the two. Divide airflow in ft³/min by specific volume in ft³/lb dry air to obtain pounds of dry air per minute.

Psychrometric chart showing a specific volume of about 13.5 cubic feet per pound of dry air and conversion of 5000 cfm to about 371 pounds of dry air per minute
Figure 4. In the example, 5,000 ft³/min ÷ 13.5 ft³/lb dry air ≈ 371 lb dry air/min.
Use the Appropriate Pressure and Air Condition

Specific volume changes with air temperature, moisture, and barometric pressure. Use a chart or software for the applicable pressure and a state point appropriate to the calculation; do not assume one air-density shortcut fits every location and condition.

Multiply Mass Flow by Enthalpy Difference

Total air-side cooling capacity is dry-air mass flow multiplied by the entering-to-leaving enthalpy difference. Multiply by 60 minutes per hour when mass flow is in pounds per minute and the answer is required in Btu/h.

Compact Equation

Total Btu/h = (CFM ÷ specific volume) × enthalpy difference × 60.

Four-step total air-side cooling calculation converting 5000 cfm to 371 pounds of dry air per minute and multiplying by a 15.2 Btu per pound enthalpy difference to obtain about 338649 Btu per hour
Figure 5. The example estimates approximately 338,649 Btu/h, or 28.2 tons, of total air-side cooling at the measured operating conditions.
Measured Capacity Is Not the Building Load

This result estimates heat transfer from the measured airstream at one operating condition. Use a recognized load calculation and manufacturer performance data when selecting equipment, and follow manufacturer procedures when evaluating equipment operation.

Convert the Humidity-Ratio Difference into Water per Hour

Multiply dry-air mass flow by the grains removed per pound of dry air. Divide by 7,000 grains per pound of water, multiply by 60 minutes per hour, and divide by approximately 8.34 pounds per gallon when a gallons-per-hour estimate is desired.

Compact Equation

Gallons per hour = (lb dry air/min × grains removed/lb dry air ÷ 7,000) × 60 ÷ 8.34.

Four-step condensate calculation using 371 pounds of dry air per minute and 58 grains removed per pound to estimate 185 pounds or 22.1 gallons of water per hour
Figure 6. The example estimates approximately 185 lb water/h, or 22.1 gal/h, during steady operation at the stated conditions.

Drain-flow caution: Actual water leaving the drain may differ during startup, cycling, coil water retention, re-evaporation, trap problems, leakage, or changing entering conditions.

Separate the Temperature and Moisture Portions Carefully

Sensible capacity is associated with lowering dry-bulb temperature. Latent capacity is associated with removing water vapor. Total capacity is the sum of the sensible and latent portions when all values use the same consistent basis.

Comparison showing example sensible capacity of about 136012 Btu per hour, latent capacity of about 202636 Btu per hour, total capacity of about 338649 Btu per hour, and sensible heat ratio of about 0.40
Figure 7. This deliberately high-dehumidification example has an estimated sensible heat ratio of approximately 0.40.

Sensible Capacity

Energy transfer associated primarily with the dry-bulb temperature change.

Latent Capacity

Energy transfer associated with water vapor condensing from the air.

Sensible Heat Ratio

SHR = sensible capacity ÷ total capacity. A lower SHR indicates a larger latent share for that operating condition.

The 40/60 Split Is Not a Rule

The sensible-to-latent split changes with entering air, leaving air, airflow, coil condition, refrigerant operation, outdoor-air load, and system control. The example’s 40% sensible and 60% latent split applies only to the example.

Write Down the Property and Unit at Every Step

A worksheet helps keep paired measurements, chart values, differences, mass flow, and final results together. Record the pressure or elevation basis, airflow source, operating mode, stabilization status, and exact measurement locations.

Psychrometric field calculation worksheet with spaces for air measurements, humidity ratio, enthalpy, specific volume, process differences, air-side calculations, and verification checks
Figure 8. Use one worksheet for the complete process so units, state points, and field conditions remain visible.

1. Stabilize and Measure

Confirm operating mode and collect representative entering, leaving, and airflow measurements.

2. Plot Both States

Use a chart or psychrometric software with the correct pressure basis.

3. Read the Properties

Record humidity ratio, enthalpy, and specific volume with their units.

4. Calculate Differences

For cooling, subtract leaving values from entering values and confirm the signs make sense.

5. Convert to Rates

Use dry-air mass flow and carry minutes, hours, grains, pounds, and gallons through each conversion.

6. Compare and Investigate

Compare the result with manufacturer data and the measured operating condition before deciding what to inspect next.

A Correct State Point Can Still Produce a Wrong Answer

Six common psychrometric calculation errors involving relative humidity, cubic feet and cfm, single enthalpy values, Btu per pound, water conversions, and treating measured capacity as building load
Figure 9. Label each value with its property and unit, then confirm that unwanted units cancel.

“Subtract the RH readings.”

Relative humidity is temperature dependent. Subtract humidity ratios to determine moisture removed per pound of dry air.

“Cubic feet and cfm are interchangeable.”

Cubic feet is volume; cfm is a volume-flow rate. Keep the per-minute time unit through the calculation.

“One enthalpy reading is capacity.”

Use the difference between entering and leaving enthalpy, then multiply by dry-air mass flow.

“Btu/lb is the same as Btu/h.”

Btu/lb dry air is energy per mass. Capacity in Btu/h is an energy-transfer rate.

“Grains can be treated as pounds.”

There are 7,000 grains in one pound. Write the conversion so the grain unit cancels.

“Measured capacity sizes the equipment.”

A field estimate describes one measured condition; it is not a building load calculation or a replacement for manufacturer performance data.

Can You Keep the Properties, Units, and Meaning Straight?

  1. Why must entering and leaving measurements represent the same airstream?
  2. What does enthalpy describe, and what are its common I-P chart units?
  3. Why is an enthalpy difference used instead of one enthalpy value?
  4. Which property should be subtracted to find moisture removed per pound of dry air?
  5. Why should relative-humidity readings not be subtracted for that purpose?
  6. What does specific volume describe?
  7. How is cfm converted to pounds of dry air per minute?
  8. What three quantities are used to calculate total air-side Btu/h in this lesson?
  9. How many grains are in one pound?
  10. Why can measured drain flow differ from calculated steady-state moisture removal?
  11. What does sensible heat ratio compare?
  12. Why must measured air-side capacity not be treated as the building load?

What You Should Have Learned

1

Reliable calculations begin with representative paired measurements, verified airflow, stable operation, and the correct pressure basis.

2

Humidity-ratio difference describes water removed per pound of dry air, while enthalpy difference describes total cooling per pound of dry air.

3

Specific volume converts volumetric airflow in cfm to dry-air mass flow in pounds per minute.

4

Total air-side capacity equals dry-air mass flow multiplied by enthalpy difference with the time units converted consistently.

5

Condensate rate comes from dry-air mass flow and humidity-ratio difference, including the required grain, pound, hour, and gallon conversions.

6

Total capacity contains sensible and latent portions, and SHR is sensible capacity divided by total capacity.

7

The sensible-to-latent split changes with the measured operating condition and is not a fixed rule.

8

An air-side estimate supports diagnosis but does not replace load calculations, equipment ratings, or manufacturer service information.

NEXT LESSON

Psychrometrics in HVAC/R Service and Troubleshooting

The next lesson applies psychrometric measurements and process patterns to comfort complaints, airflow checks, coil performance, ventilation, humidity control, and systematic field troubleshooting.