This is an old tester the engineers used to use for testing the mains socket
and veracity of earths on sockets etc. It is quite useless nowadays with RCD/
ELCB protected supplies as it WILL ALWAYS TRIP THEM!
___________
PRINCIPLES
The meter provides a single half wave pulse of current (30A) from live to earth
through a known resistor. The peak voltage across the resistor will equal the
supply voltage less the loss due to earth line resistance/impedance.
If the Earth and Live resistance equals R the voltage across R will be halved.
This voltage is compared to the mains so that variation in the mains does not
alter meter reading. Because this is fast pulse test (10mS) the earth circuit
"impedance" to the pulse rather than just the DC resistance is measured. Also
by using a full 30A peak current the capability of the wiring is actually
tested. E.g. fine wire strands that may pass the resistance test would be blown
up passing this current! This makes the test, what is required for a PROPER
SAFETY TEST, even though it hazards other kit plugged in at the time.
METER CIRCUIT
CIRCUIT OPERATION
On connecting the mains the 2 neons should light, indication the mains is SAFE
to test. The 5A fuse handles the 30A pulse OK.
The transformer's 16V winding charges up the 47uF capacitor via D1 ready to
trigger the SCR. The 8V winding via D3 makes a -11V mains reference rail.
On testing, a single half cycle +ve peak voltage appears across the 30 Watt 10R
(one test per min MAX) and it is attenuated with 1K & 33R and compared to the
-11V rail, the resultant peak voltage is fed via D2 (not shorted in test mode)
to the u22 storage cap.
The voltage across the cap is then read with the FET buffered meter, with its
floating regulated power supply. Zero offset & meter gain presets finish off
the calibration.
Z VALUES
To quickly blow a 13A fuse, a current > 26A must flow. So at 220V that needs a
total loop resistance < 9 ohm. However with high current main ring circuits of
30A to blow a ring fuse quickly needs a current > 60A, which needs loop
resistance < 3 ohm. These are much lower values than you can get with external
earths!
I once tested a large unused radio tower & earth system with a simple if
dangous electric kettle test (no kit on tower) and I was horrified to find it
was as high as 14 ohm!
See my buls "Earths", "Edgcume Peebles Megger & Low R". "Maplin Mains Meter
2000MU-UK", & also "Mains Power Protection".
Why don't U send an interesting bul?
73 de John G8MNY @ GB7CIP