Condenser Subcooling

Subcooling occurs after refrigerant vapor has completely condensed into liquid and additional heat is removed from that liquid refrigerant.

In an air-cooled condenser, this normally occurs in the final portion of the condenser coil. Measuring subcooling requires two temperatures: the refrigerant condensing temperature and the actual liquid-line temperature leaving the condenser.

This lesson explains where subcooling occurs, how the two required temperatures are obtained, and how condenser subcooling is calculated.

What You Will Learn

By the end of this lesson you should be able to:

1

Explain what subcooling means.

Recognize that subcooling occurs after refrigerant has completely condensed into liquid.

2

Identify where condenser subcooling occurs.

Recognize the final few passes of the condenser as the area identified in the source lesson where subcooling takes place.

3

Determine condensing temperature.

Use condenser pressure and the refrigerant pressure-temperature relationship to determine the condensing-point temperature.

4

Measure liquid-line temperature.

Use a clamp-on thermometer on the liquid line at the condenser outlet.

5

Calculate condenser subcooling.

Subtract the leaving liquid-line temperature from the condensing temperature.

What Is Subcooling?

During the condensing portion of the condenser, refrigerant changes from vapor to liquid.

Once all of the refrigerant has become liquid, additional heat can still be removed. When the liquid refrigerant temperature falls below its condensing temperature, the refrigerant is subcooled.

Technician Point

Subcooling occurs after condensation is complete.

The refrigerant is already liquid. Additional heat removal lowers the temperature of that liquid below the condensing-point temperature.

Where Does Subcooling Occur?

The source lesson states that subcooling takes place in the last few passes of the condenser. :contentReference[oaicite:1]{index=1}

1

Superheated Vapor Enters

Hot, high-pressure refrigerant vapor enters the condenser through the compressor discharge line.

2

Refrigerant Condenses

Heat is removed until the refrigerant changes completely from vapor to liquid.

3

Liquid Is Subcooled

Additional heat is removed from the liquid refrigerant in the final portion of the condenser.

4

Subcooled Liquid Leaves

High-pressure liquid refrigerant leaves the condenser through the liquid line.

Measuring Condenser Subcooling

Two values are required to determine condenser subcooling:

Condensing temperature and liquid-line temperature.

Air-cooled condenser showing high-side pressure measurement and a clamp-on thermometer on the liquid line for calculating condenser subcooling.

Figure 1. Condenser subcooling is determined from condensing temperature and the measured liquid-line temperature.

About the Refrigerant Inlet Shown in Figure 1

The hot, high-pressure vapor entering the condenser comes from the compressor discharge line.

The compressor may be physically remote from the condenser. The illustration shows the refrigerant connection to the condenser, not a requirement that the compressor be located inside or immediately beside the condenser assembly.

STEP 1

Determine Condenser Pressure

The first value needed is the refrigerant pressure in the condenser.

The source lesson explains that the condensing-point temperature is found by converting condenser pressure to temperature. :contentReference[oaicite:2]{index=2}

Important

The pressure reading itself is not the condensing temperature.

The condenser pressure must first be converted to the corresponding temperature for the refrigerant being used.

STEP 2

Convert Pressure to Condensing Temperature

Use the refrigerant pressure-temperature relationship to convert the measured condenser pressure into the corresponding condensing-point temperature.

1

Measure condenser pressure

Obtain the high-side refrigerant pressure.

2

Use the pressure-temperature relationship

Find the temperature corresponding to that pressure for the refrigerant in the system.

3

Determine condensing temperature

This becomes the first temperature used in the subcooling calculation.

STEP 3

Measure the Leaving Liquid-Line Temperature

The source instructs the technician to measure refrigerant temperature by placing a clamp-on thermometer on the liquid line at the condenser outlet. :contentReference[oaicite:3]{index=3}

Measurement Location

Measure the liquid line where the refrigerant leaves the condenser.

Measurement Tool

Use a clamp-on thermometer as described in the source lesson.

Technician Point

The pressure-derived condensing temperature and the measured liquid-line temperature are two different values.

Both are required to calculate subcooling.

STEP 4

Calculate Subcooling

The source defines the calculation as the condensing-point temperature minus the temperature of the refrigerant leaving the condenser. :contentReference[oaicite:4]{index=4}

CONDENSER SUBCOOLING

Subcooling = Condensing Temperature − Liquid-Line Temperature

Subcooling Example

The illustration used in this lesson provides a simple example of the calculation.

Condensing temperature
110°F
Liquid-line temperature
92°F
Subcooling
110°F − 92°F = 18°F

Result

The liquid refrigerant is 18°F below its condensing temperature in this example.

What Does the Subcooling Number Represent?

The subcooling value represents the temperature difference between the refrigerant’s condensing temperature and its actual temperature after leaving the condenser as liquid.

Condensing Temperature

The temperature determined from the condenser refrigerant pressure.

Liquid-Line Temperature

The actual refrigerant temperature measured at the condenser outlet.

Subcooling

The difference between those two temperatures is the amount of condenser subcooling.

Put the Measurement Procedure Together

1

Measure Condenser Pressure

Obtain the high-side refrigerant pressure.

2

Find Condensing Temperature

Convert condenser pressure to the corresponding refrigerant temperature.

3

Measure Liquid-Line Temperature

Place a clamp-on thermometer on the liquid line at the condenser outlet.

4

Subtract

Subtract the liquid-line temperature from the condensing temperature.

Keep the Two Temperatures Straight

The most important part of the procedure is understanding where each temperature comes from.

Do Not Use Pressure as Temperature

Condenser pressure must first be converted to the corresponding refrigerant condensing temperature.

Measure the Liquid Line

The second temperature is the actual refrigerant temperature measured at the condenser outlet.

Subtract in the Correct Order

Condensing temperature comes first, followed by the leaving liquid-line temperature.

Put the Concepts Together

1

Subcooling occurs after the refrigerant has completely condensed into liquid.

2

The source places subcooling in the last few passes of the condenser.

3

Condenser pressure is converted to the corresponding refrigerant condensing temperature.

4

The leaving liquid-line temperature is measured with a clamp-on thermometer at the condenser outlet.

5

Subcooling equals condensing temperature minus liquid-line temperature.

6

The compressor discharge line supplying the condenser may originate from a compressor located remotely from the condenser.

CHECK YOUR UNDERSTANDING

Can You Calculate Condenser Subcooling?

You should be able to answer these questions before continuing.

1. When in the condensing process does subcooling begin?

2. Where does the source lesson say subcooling occurs in the condenser?

3. What pressure must be measured to determine condensing temperature?

4. How is condenser pressure converted into condensing temperature?

5. Where should the liquid-line temperature be measured?

6. What type of thermometer does the source specify?

7. What is the formula for condenser subcooling?

8. If condensing temperature is 110°F and liquid-line temperature is 92°F, what is the subcooling?

9. Does the compressor shown by implication in the condenser inlet have to be physically next to the condenser?

What You Should Have Learned

1

Subcooling is additional cooling of liquid refrigerant after condensation is complete.

2

The source identifies the final few condenser passes as the area where subcooling occurs.

3

Condensing temperature is determined from condenser refrigerant pressure.

4

Liquid-line temperature is measured at the condenser outlet with a clamp-on thermometer.

5

Condenser subcooling is calculated by subtracting liquid-line temperature from condensing temperature.

6

The two temperatures used in the calculation come from different measurements and should not be confused.

Two Temperatures, One Calculation

Condenser subcooling requires only two temperature values once condenser pressure has been converted correctly:

Condensing Temperature − Liquid-Line Temperature = Subcooling

The key is knowing where each value comes from and measuring the liquid-line temperature at the condenser outlet.